In uk.tech.broadcast, on Sun, 1 Jun 2008 17:23:10, Zathras wrote:

My broadcasting experience is that we'd have had fewer bits of broken
kit and fewer outages if we hadn't had any UPSs at all!


Agreed!

At out new building, we don't have any - just two kinetic batteries
and a generator that comes up before the KB's spin down.


Outstanding idea.

--
Jim Crowther
  #22  
Old June 1st 08, 09:59 PM posted to uk.tech.broadcast,uk.tech.digital-tv
:Jerry:
external usenet poster
 
Posts: 345
Default Catastophic failure on ITV


"Zathras" wrote in message
...
snip

At out new building, we don't have any - just two kinetic batteries
and a generator that comes up before the KB's spin down.


I assume by "kinetic batteries" you mean 'motor-flywheel-generators',
if so, how is this implemented?


  #23  
Old June 1st 08, 11:01 PM posted to uk.tech.broadcast,uk.tech.digital-tv
Dave Liquorice[_2_]
external usenet poster
 
Posts: 253
Default Catastophic failure on ITV

On Sun, 01 Jun 2008 17:23:10 +0100, Zathras wrote:

At out new building, we don't have any - just two kinetic batteries
and a generator that comes up before the KB's spin down.


Hopefully the generator comes up before the kinetics spin down...

--
Cheers
Dave.



  #24  
Old June 2nd 08, 12:02 AM posted to uk.tech.broadcast,uk.tech.digital-tv
Andy Champ
external usenet poster
 
Posts: 145
Default Catastophic failure on ITV

Java Jive wrote:
Somehow, I can't show any surprise ...

snips long scary story

Our critical servers are all fitted with dual PSUs. The idea is that
one is fed from the UPS, and one straight from the mains. Lose the
mains, and the UPS kicks in. Lose the UPS, and they run straight from
the mains. (we're moving machine rooms soon, and as I now "own" some of
the servers, I'll check that they really are like that in their new home)

Repeat after me: "No Single Point Of Failure"

Andy
  #25  
Old June 2nd 08, 12:21 AM posted to uk.tech.broadcast,uk.tech.digital-tv
Andy Burns[_4_]
external usenet poster
 
Posts: 205
Default Catastophic failure on ITV

On 01/06/2008 23:02, Andy Champ wrote:

Our critical servers are all fitted with dual PSUs. The idea is that
one is fed from the UPS, and one straight from the mains. Lose the
mains, and the UPS kicks in. Lose the UPS, and they run straight from
the mains.


Early morning generator test occurs, you loose mains for a few seconds,
no problem UPS cuts in, generator starts, that extra server you added
recently increases the inrush current as half of your PSUs come back on
line at once, mains MCB trips, current drawn by the other half of your
PSUs is double normal, workload increases on the servers as people start
logging on for the day, servers draw that critical few extra amps, a
circuit breaker on the UPS reaches its limit and it trips, it goes dark
and quiet ...



  #26  
Old June 2nd 08, 01:30 AM posted to uk.tech.broadcast,uk.tech.digital-tv
Dave Liquorice[_2_]
external usenet poster
 
Posts: 253
Default Catastophic failure on ITV

On Sun, 01 Jun 2008 23:21:28 +0100, Andy Burns wrote:

Early morning generator test occurs, you loose mains for a few seconds,
no problem UPS cuts in, generator starts, that extra server you added
recently increases the inrush current as half of your PSUs come back on
line at once, mains MCB trips,


AWOOGA, AWOOGA, blooming great alarm goes off triggered by detecting
voltage across the MCB(s)...

--
Cheers
Dave.



  #27  
Old June 2nd 08, 08:56 AM posted to uk.tech.broadcast,uk.tech.digital-tv
Clive
external usenet poster
 
Posts: 23
Default Catastophic failure on ITV


"Richard Tobin" wrote in message
...
In article ,
:Jerry: wrote:

It seems from the DS posting made today, that the UPS let out a nice
fat spike.


There is some what of an irony in that, of all the devices to *cause*
an outage?! :~(


In 30 years of using computers, I have experienced innumerable
computer outages because of UPSes being installed, removed, serviced,
or exploding, and have never once had my computer stay up, or even
shut down in an orderly manner, when the mains was cut.



Heading up to the millenium I was responsible for maintaining a large test
facility and we were pulled in 4 weekends in a row to test the power backup
facilities. First weekend, after the power had been cut, the electricians
discovered that no one had thought to put diesel in the generator. Second
weekend the UPS went bang. Third weekend it was discovered that my test
facility was not actually connected into the power backup network. Fourth
weekend, power stayed up, but half the equipment went down because of spikes
on the voltage at switching.

The fifth weekend was the millenium itself, thankfully power backup was
never needed.

//Clive.



  #28  
Old June 2nd 08, 09:15 AM posted to uk.tech.broadcast,uk.tech.digital-tv
tony sayer
external usenet poster
 
Posts: 4,132
Default Catastophic failure on ITV

In article id, Jim
Crowther scribeth thus
In uk.tech.broadcast, on Sun, 1 Jun 2008 17:23:10, Zathras wrote:

My broadcasting experience is that we'd have had fewer bits of broken
kit and fewer outages if we hadn't had any UPSs at all!


Agreed!

At out new building, we don't have any - just two kinetic batteries
and a generator that comes up before the KB's spin down.


Outstanding idea.


Yep UPS's aren't the most reliable backup power. We directly float quite
a bit of Telecoms equipment off battery banks at either 24 or 48 volts,

Much more reliable that whopping it back up to 230 volts)..
--
Tony Sayer



  #29  
Old June 2nd 08, 10:42 AM posted to uk.tech.broadcast,uk.tech.digital-tv
Zathras
external usenet poster
 
Posts: 195
Default Catastophic failure on ITV

On Sun, 01 Jun 2008 22:01:21 +0100 (BST), "Dave Liquorice"
wrote:

On Sun, 01 Jun 2008 17:23:10 +0100, Zathras wrote:

At out new building, we don't have any - just two kinetic batteries
and a generator that comes up before the KB's spin down.


Hopefully the generator comes up before the kinetics spin down...


It's regularly run, tested and maintained - if it's like our last one,
probably a twin engine unit. Totally reliable IME.

--
Z
  #30  
Old June 2nd 08, 10:50 AM posted to uk.tech.broadcast,uk.tech.digital-tv
Zathras
external usenet poster
 
Posts: 195
Default Catastophic failure on ITV

On Sun, 1 Jun 2008 20:59:13 +0100, ":Jerry:"
wrote:


"Zathras" wrote in message
.. .
snip

At out new building, we don't have any - just two kinetic batteries
and a generator that comes up before the KB's spin down.


I assume by "kinetic batteries" you mean 'motor-flywheel-generators',
if so, how is this implemented?


Two contra-rotating units (fearlessly) located on the roof. They
supply energy instantly and for a longer time than the generator takes
to start and stabilise. I don't have any more detail of our
installation so for more than that, Google is the place to look - KBs
are amazing devices!

--
Z
 




Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Forum Jump

Similar Threads
Thread Thread Starter Forum Replies Last Post
Passthrough failure on Sky+ ? Tumbleweed UK sky 12 January 29th 06 11:14 AM
DLP and Power Failure Bill Oertell High definition TV 10 December 16th 04 01:38 PM
Hughes DVR failure Owner Tivo personal television 3 April 8th 04 02:26 AM
Disk failure Chris Tivo personal television 4 January 25th 04 10:09 PM
Sky+ Failure Andrew Corcoran UK sky 2 September 30th 03 11:10 PM


All times are GMT +1. The time now is 03:34 PM.


Powered by vBulletin® Version 3.6.4
Copyright ©2000 - 2021, Jelsoft Enterprises Ltd.
Copyright ©2004-2021 HomeCinemaBanter.
The comments are property of their posters.